piwik image

DAIKIN DCS601C71

DAIKIN DCS601C71 Intelligent Touch Controller, 24 VAC, 50/60 Hz

DAIKIN DCS601C71

The iTouch is our advanced centralized controller. It can control up to 64 indoor unit groups (128 indoor units). It has independent cool and heat setpoints for occupied and unoccupied conditions. The iTouch Controller provides building owners, facilities/premises managers and maintenance operators refined and energy efficient control of Daikin VRVIII, VRV WIII, VRVIII-S and/or mixed VRVIII/VRV-IIIS/SkyAir indoor units. With its user friendly color icons and scheduling capabilities, this controller makes management of indoor units and other facilities equipment easy. The iTouch Controller is linked directly to the system via a Daikin DIII-Net connection without the need for a PC. Supports centralized control remotely using a PC with a Web browser (Optional).

DAIKIN Intelligent Touch Controller, 24 VAC, 50/60 Hz, 85% or Less RH Non-Condensing Humidity Rating, 32 - 104 deg F, 5-25/32 in H x 9-1/16 in W x 4-7/32 in D

Voltage Rating      :      24 VAC
Frequency Rating      :      50/60 Hz
Humidity Rating      :      85% or Less RH Non-Condensing
Temperature Rating      :      32 - 104 deg F
Dimensions      :      5-25/32 in H x 9-1/16 in W x 4-7/32 in D
  • Capable of controlling zone(s) or group(s) of upto 64 indoor unit groups (128 indoor units)
  • On/off
  • Operation mode (cool, heat, fan, dry)
  • Independent cooling and heating setpoints in the occupied mode
  • Independent setup (cooling) and setback (heating) setpoints in the unoccupied mode adjustable to 40 - 95 deg F
  • Fan speed
  • Airflow direction (dependent upon indoor unit type)
  • Setpoint range limitation
  • Remote controller permit/prohibit of On/Off, mode and setpoint
  • Touch screen (display) lockout
  • Provides battery backup power for up to two-year in total time for the clock
  • Weekly schedule settings, selectable weekly patterns 7 day, weekday + weekend (5 + 2), weekday + saturday + sunday (5 + 1 + 1), eight independent schedules configurable with up to eight events for each schedule
  • Independent cooling and heating setpoints when unit is on (occupied), independent setback setpoints cool and heat modes
  • Auto-changeover
  • Interlock feature for use with 3rd party equipment (DOAS, dampers, occupancy sensing and more) to automatically control groups or zones corresponding to the change of the operation states or the on/off states of any group and more
  • On/off based monitoring and control of equipment
  • Manual or scheduled operation of equipment
  • Operation based upon interlock with VRV indoor unit group(s), monitor equipment error/alarm status, supports force shutdown of associated indoor unit groups
  • Communication -Dlll-Net x 1 AC equipment communication line, 10Base-T web option, PCMCIA slot flash memory card used for PPD
  • 64-maximum groups, 128-maximum indoor units, 10-maximum outdoor units