Bard® 8301-061

Bard® 8301-061 Gas Detector, Hydrogen Gas

Bard® 8301-061

The VDC HGD hydrogen gas detector is designed for hydrogen gas detection device for battery rooms and shelters. When used in conjunction with the PLC controlled DA/DL series wall mount unit, the HGD can be used to detect hydrogen gas as low as 1% volume and operate the wall mount unit economizer and indoor blower to bring in outdoor air. At 2% volume, a warning alarm will sound and an alarm signal will be activated through the LC controller.

Bard® Gas Detector, 17-60 VDC, Hydrogen Gas, Wall Mounting, For Use With: DA/DL Series Units with PLC Logic Boards, 14 to 104 deg F, 7 in H x 4-1/2 in W x 2-1/4 in D

Voltage Rating      :      17-60 VDC
Gas Type      :      Hydrogen
Mounting Type      :      Wall
Suitable For Use With      :      DA/DL Series Units with PLC Logic Boards
Temperature Rating      :      14 to 104 deg F
Dimensions      :      7 in H x 4-1/2 in W x 2-1/4 in D
  • Sensor is pre-calibrated and requires no adjustment, at higher elevations and temperatures, the sensor may activate the alarm functionality at slightly lower hydrogen levels
  • Push to test button to verify sensor electronic circuitry
  • The sensor detects several other combustible gases in addition to hydrogen-ethanol, isobutane, methane, propane, its sensitivity to these other gasses, however, is much lower than its sensitivity to hydrogen, this should not noticeably affect its operation
  • Use 18 ga SJT 3 conductor PVC jacketed cable for power connection, use 14 ga wire for relay operation
  • 5 years sensor life