piwik image

Robertshaw® 780-002

Robertshaw® 780 Series 780-002 Ignition Control Module, 24 VAC, 1.5 A, 50/60

Robertshaw® 780-002

The Robertshaw 780 series pilot controls Uni-Kits feature a flame sense circuit that will work equally well on a 1-rod (local sense) or a 2-rod (remote sense) application. The automatic recycle features assure that, in the event of flame failure, main gas is disabled and the spark repetition sequence is restarted until pilot gas is ignited. Only after pilot ignition has been re-established can main gas be returned to the burner.

Robertshaw® Ignition Control Module, 780 Series, 24 VAC, 1.5 A, 50/60 Hz, 360 s Pre Purge, 90 s Ignition Trial Time Delay, 95% RH Non-Condensing at 104 deg F Humidity Rating, -40 to 175 deg F

Series      :      780 Series
Voltage Rating      :      24 VAC
Amperage Rating      :      1.5 A
Frequency Rating      :      50/60 Hz
Time Delay      :      360 s Pre Purge, 90 s Ignition Trial
Humidity Rating      :      95% RH Non-Condensing at 104 deg F
Temperature Rating      :      -40 to 175 deg F
  • Replaces one and/or two-rod systems
  • Reduces truck stock inventory, saving space and money
  • Easy-to-install with complete in-depth installation instructions
  • Pilot and main valves draw 1 A at 0.5 power factor
  • Combined load at 1.5 A at 0.4 power factor
  • Each ignition period is followed by a 6 min time delay between ignition attempts
  • 3 - 4 sec per spark rate
  • 0.7 mA DC flame sense current at 25 deg C
  • 0.8 sec flame failure re-ignition time
  • 0.7 A thermostat anticipator setting
  • 20 VA at 24 VAC transformer
  • 1/4 in spades and Molex plug electrical connection